Classification : Dynisco / Controller
Country: Taiwan
Phone: 886-4-2631-3001
Fax: 886-4-2631-7717
Contact Person: Harrison Chang
The ATC990 Process Controller provides a cost-effective way to control a single process parameter, such as for a plastics extruder. Designed to improve user efficiency many features are integrated to reduce commissioning time, simplify operation and minimize maintenance downtime. Reliably auto-tune and alarm on strain gauge, DC voltage, temperature or current inputs. The ATC990 can also control differential pressure when an optional secondary strain gauge input is used.
■ Auto-tuning control in a discrete 1/4 DN package
■ Graphical/text LCD Display with color change LED backlight on alarm (red/green)
■ Graphical trend view of process alarms & events as standard
■ Easy to use Setup Wizard
■ Single loop control
■ USB port option logs process values, set points and alarms to .csv file for use with spreadsheets
■ Modbus RS-485 and Modbus TCP Ethernet supported
■ BlueControl configuration and commissioning software option
■ Graphical/text LCD Display with color change LED backlight on alarm (red/green)
■ Graphical trend view of process alarms & events as standard
■ Easy to use Setup Wizard
■ Single loop control
■ USB port option logs process values, set points and alarms to .csv file for use with spreadsheets
■ Modbus RS-485 and Modbus TCP Ethernet supported
■ BlueControl configuration and commissioning software option
| Instrument Type: | Digital, panel-mount PID closed loop controller |
| Display: | 160 x 80 Monochromatic Graphical LCD with backlight |
| Thermocouple: | ±0.1% of full range, ±1LSD, (±1°C for internal CJC if enabled) |
| DC Linear: | ±0.1% of full range, ±1LSD |
| Sampling Time: | 50mS, typical |
| Input: | Strain gauge, Thermocouple or linear (Vdc, mA) |
| Strain Gauge: | 350 to 5000Ω, 1.4 to 4mV/V, excitation 10V ±7% |
| Linear Input: |
0 to 5Vdc and 0
to 10Vdc, 0 to 20mA and 4 to 20mA |
| Input Signal: | -25 to 125% full scale (approximately -10mV to +50mV) |
| Input Impedance: |
<10Ω for
linear current input >165kΩ for linear voltage input |
| Shunt Calibration: | With or without resistor (40 to 100%) |
| Digital: | 4 programmable voltage-free contact closure |
| Alarm Type: | SPST 2A max @ 240Vac resistive load Dual relays have shared common |
| Alarm Number: | 3 standard |
| Alarm Update Time: | 100mS, typical |
| Type (Retransmission): | 0-5Vdc and 0-10Vdc, 0-20mA and 4-20mA |
| Type (Control): | 0-5Vdc and0-10Vdc (2% under/over drive) 0-20mA and 4-20mA |
| Resolution: | 15 3/4 bit |
| Accuracy: | ±0.1% of output span (mA @ <500Ω, V @ >500Ω) |
| Type: | Adaptive auto-tuning algorithm |
| Type: | Isolated RS-485 |
| Protocol: | Modbus RTU |